Stahlband XLPE Isoliertes Stromkabel(2-4 Kerne) Parameter
Cross-sectional Area (mm2) | No.& diameter of wire (N/mm) | Average overall diameter (mm) | Reference weight (kg/km) | Conductor Resistance(Ω/km) 20ºC Max | ||||
2 | 3 | 4 | 2 | 3 | 4 | |||
1.5 | 1/1.38 | 13.0 | 13.5 | 14.2 | 259 | 286 | 321 | 12.10 |
2.5 | 1/1.78 | 13.8 | 14.3 | 15.2 | 302 | 337 | 386 | 7.41 |
4.0 | 7/0.85 | 16.2 | 16.9 | 18.1 | 415 | 469 | 546 | 4.61 |
6.0 | 7/1.04 | 17.2 | 18.0 | 19.3 | 487 | 560 | 662 | 3.08 |
10 | 7/1.35 | 19.2 | 20.1 | 21.7 | 639 | 752 | 902 | 1.83 |
16 | 7/1.70 | 21.0 | 22.3 | 24.1 | 812 | 997 | 1212 | 1.15 |
25 | 10/1.83 | 18.5 | 20.9 | 23.1 | 817 | 1120 | 1416 | 0.727 |
35 | 14/1.8 | 21.2 | 24.0 | 26.7 | 1081 | 1493 | 1906 | 0.524 |
50 | 19/1.83 | 23.9 | 27.2 | 30.3 | 1409 | 1964 | 2527 | 0.387 |
70 | 27/1.83 | 26.2 | 30.6 | 34.3 | 1840 | 2619 | 3400 | 0.268 |
95 | 37/1.83 | 29.9 | 34.6 | 40.8 | 2428 | 3477 | 4952 | 0.193 |
120 | 30/2.32 | 32.1 | 38.9 | 44.1 | 2980 | 4688 | 6064 | 0.153 |
150 | 37/2.32 | 36.6 | 42.3 | 48.2 | 3965 | 5619 | 7281 | 0.124 |
185 | 37/2.52 | 39.7 | 46.0 | 52.8 | 4725 | 6726 | 8767 | 0.0991 |
240 | 48/2.52 | 45.1 | 52.6 | 60.3 | 6054 | 8650 | 11249 | 0.0754 |
300 | 61/2.52 | 49.1 | 57.9 | 66.2 | 7406 | 10651 | 13907 | 0.0601 |
400 | 61/2.95 | 54.7 | 65.0 | 73.6 | 9709 | 14068 | 18365 | 0.0470 |
Circular dirigent <= 16mm2; Shaped dirigent >= 25mm2
Beschreibung des Stahlbandes XLPE Isoliertes Stromkabel(2-4 Kerne)
Verschiedenes 8 67; Rate Temperatur: 90 o C
[]; Verschiedenes 8 67; Nennspannung: 600/1000V 0000
[]; Referenzstandard: GB/T12706, IE C 60502
8 607; M o dell: YJV
[8 6267]; gef o rmte Kupferleiter
[8 6262626267]; Is o liert mit Querverbindung aus P o lyethylenInsgesamt verglast; Flammschutzmittel PV C
Anwendung aus Stahlband XLPE Isolier Power Cable(2-4 Kerne)
für die unterirdische Installation in Transport- und Stromverteilungen