Kupferband Screened Control Cable Parameter
Cross-Sectional Area | Thickness of Insulation | Thickness of Copper Tape | Thickness of Sheath | Overall Diameter (mm) | Min resistance of insulation at 70℃ | Max.D.C resistance of at 20℃ | Approx Weight | Approx Weight | |
mm² | mm | mm | mm | min | max | MΩ/km | MΩ/km | (kg/km) | (kg/km) |
4x0.75 | 0.6 | 0.05-0.1 | 1.2 | 8.1 | 9.7 | 0.012 | 24.5 | 144 | 144 |
4x1 | 0.6 | 0.05-0.1 | 1.2 | 8.4 | 10.2 | 0.011 | 18.1 | 153 | 153 |
4x1.5 | 0.7 | 0.05-0.1 | 1.2 | 9.5 | 11.4 | 0.011 | 12.1 | 190 | 190 |
4x2.5 | 0.8 | 0.05-0.1 | 1.5 | 10.9 | 13.1 | 0.01 | 7.41 | 276 | 276 |
4x4 | 0.8 | 0.05-0.1 | 1.5 | 12.5 | 15.1 | 0.0085 | 4.61 | 367 | 367 |
4x6 | 0.8 | 0.05-0.1 | 1.5 | 13.6 | 16.5 | 0.007 | 3.08 | 467 | 467 |
4x10 | 1 | 0.05-0.1 | 1.7 | 17.1 | 20.7 | 0.0065 | 1.83 | 728 | 728 |
7x0.75 | 0.6 | 0.05-0.1 | 1.2 | 9.3 | 11.2 | 0.012 | 24.5 | 178 | 178 |
7x1.0 | 0.6 | 0.05-0.1 | 1.2 | 9.7 | 11.7 | 0.011 | 18.1 | 209 | 209 |
7x1.5 | 0.7 | 0.05-0.1 | 1.5 | 11 | 13.3 | 0.011 | 12.1 | 239 | 239 |
7x2.5 | 0.8 | 0.05-0.1 | 1.5 | 13.3 | 16.1 | 0.01 | 7.41 | 398 | 398 |
7x4 | 0.8 | 0.05-0.1 | 1.5 | 14.6 | 17.6 | 0.0085 | 4.61 | 528 | 528 |
7x6 | 0.8 | 0.05-0.1 | 1.5 | 16 | 19.4 | 0.007 | 3.08 | 717 | 717 |
7x10 | 1 | 0.05-0.1 | 1.7 | 20.7 | 25.1 | 0.0065 | 1.83 | 1145 | 1145 |
10x0.75 | 0.6 | 0.05-0.1 | 1.5 | 11.3 | 13.7 | 0.012 | 24.5 | 214 | 214 |
10x1 | 0.6 | 0.05-0.1 | 1.5 | 12.5 | 15.1 | 0.011 | 18.1 | 300 | 300 |
10x1.5 | 0.7 | 0.05-0.1 | 1.5 | 14.2 | 17.2 | 0.011 | 12.1 | 367 | 367 |
10x2.5 | 0.8 | 0.05-0.1 | 1.7 | 16.5 | 20 | 0.01 | 7.41 | 572 | 572 |
10x4 | 0.8 | 0.05-0.1 | 1.7 | 18.6 | 22.5 | 0.0085 | 4.61 | 787 | 787 |
10x6 | 0.8 | 0.05-0.1 | 1.7 | 20.5 | 24.8 | 0.007 | 3.08 | 992 | 992 |
Beschreibung des Überwachungskabels für Kupferbänder
Dirigent: Solid or Stranded Copper
Isolierung: PVC/PVC(XLPE)
Screen: Copper Tape Screen
Sheath: PVC
Rate d Spannungen: 450/750V
Max. Kontinuierliche Arbeitstemperatur vonconductor:70
Bei Kurzschluss (Max. Dauer 5s) die Max.
Temperatur des Leiters nicht höher als 160°C
Umgebungstemperatur der Anlage nicht weniger als 0°C.
Standard: IEC 60227, IEC60228, AS/NZS 5000.2
China Standard: GG9330
Anwendung von Überwachungskabel für Kupferbänder
Das Steuerkabel mit Kupferbandschirm ist feuchtigkeitsbeständig, korrosionsbeständig und schadensicher.Diese Kupferbandschirm-Steuerkabel, die weit verbreitet als Verbindungsdraht für die Isolierung von Instrumenten, Steuergeräten und Stromverteilungsanlagen verwendet werden.