Al & Cu Luftisolierung Kabelparameter
Nominal Cross Section mm² | The Resistance 20ºC≤Ω/km | Conductor Drawing Pressure ≥N | |||||
Hard Cu Core | Soft Cu Core | Al Core | Aluminum alloy | Hard Cu Core | Al Core | Aluminum Alloy | |
10 | 1.830 | 3.080 | |||||
16 | 1.150 | 1.910 | |||||
25 | 0.749 | 0.727 | 1.200 | 1.393 | 8465 | 3762 | 6284 |
35 | 0.540 | 0.524 | 0.868 | 1.007 | 11731 | 5177 | 8800 |
50 | 0.399 | 0.387 | 0.641 | 0.744 | 16502 | 7011 | 12569 |
70 | 0.276 | 0.268 | 0.443 | 0.514 | 23461 | 10354 | 17596 |
95 | 0.199 | 0.268 | 0.320 | 0.371 | 31759 | 13727 | 23880 |
120 | 0.158 | 0.153 | 0.253 | 0.294 | 39911 | 17339 | 30164 |
150 | 0.128 | - | 0.206 | 0.239 | 49505 | 21033 | 37706 |
185 | 0.1021 | - | 0.164 | 0.190 | 61846 | 26732 | 46503 |
240 | 0.0777 | - | 0.125 | 0.145 | 79832 | 34679 | 60329 |
300 | 0.0619 | - | 0.100 | 0.116 | 99788 | 43349 | 75411 |
400 | 0.0484 | - | 0.0778 | 0.0904 | 133040 | 55707 | 10548 |
Beschreibung von Al && Cu Luftisolierkabel
Die Luftkabel werden wie folgt bezeichnet:
1.Cu core XLPE isolierte Antennenkabel.
2.Soft Cu Core XLPE isolierte Antenne Overhead Kabel
3.Al core XLPE isolierte Antenne Overhead Kabel.
4.Aluminium Legierung Pflege XLPE isolierte Antenne Overhead Kabel
5.Nennspannung 1kv
6.Der Betriebstemp ist nicht weniger als -20ºC.
7.standard IEC, BS AS und China&";s nationale Norm
Anwendung von Al & Cu Luftisolierkabel
Diese Antennen oder Oberleitungen sind Stromkabel-Serien zur Übertragung von Strom in einer Oberleitung die beste Wahl für den Bau und die Umwandlung von elektrischem Netz ist es die am besten geeignete Produktsicherheit und Wartung der Linie und eines Produkts.Der weiche Kupferkern wird mit Leitungen des Transformators verwendet.
Schichtung: das Verlegen von Luftseilen als Eingangsdrähte sollte Kabel eine gewisse Entfernung von den Bäumen halten.